| BATTERY
CHARGER for stationary purposes, lift, platform SYSTEM LBML/HE Charging principle WU |
Back to menu: |
|
| FULLAUTOMATIC * * * * * * * * * * * | SOFT START |
| GENERAL
The latest development in the electronic area have been used for these battery chargers. The demand of the battery manufactures has been fulfilled, so the battery obtains highest possible capacity. N.B. The battery charger may only be connected to the DC voltage for which it is designed. (Look up the rating plate). RANGE OF APPLICATION Charging of: Lead/acid batteries Sealed maintenancefree batteries Ni-Cd batteries and so on CHARGING PRINCIPLE, WU Charges in accordance to DIN 41774/ 41773, decreasing current/constant vol- tage. CONNECTION 1. Connect the charging cable to the battery by a firm connection. 2. Connect the mains. The charging soft start (red and yellow LED 1 flashes) and after 5 seconds the charging is in function. (Red LED is illuminated). NB! The battery charger may only be connected to the DC voltage for which it is designed. (Look up the rating plate). |
THE
CHARGING EVENT When the charging has started, the fullautomatic battery charger runs and controls the whole charging event. At consumption the battery charger charges automatically again. The event can be followed by the coloured LED's. Red LED: - illuminates by main - charging flashes by error Yellow LED 1: - illuminates when the given voltage has been reached Yellow LED 2: - illuminates by I < 30% Green LED: - illuminates when the battery is fully charged - flashes if low battery voltage - flashes for missing battery Red and yellow LED 1: - flashing while soft start (about 5 seconds) DISCONNECTION OF BATTERY Turn off the mains to the battery charger if you disconnect the battery. |
| LED INDICATION: | Back to menu: |
|
Red LED: - illuminates by main charging - flashes by error - flashes by to high battery voltage |
Mains and battery connected correct - Battery voltage is higher than the adjusted value |
| Yellow
LED 1: - illuminates when the given voltage has been reached |
The gassingpoint of the battery has been reached been reached |
|
Yellow LED 2: - illuminates by I < 30% |
Main current is less than 30% of nominal current |
| Green
LED: - illuminates when the battery is fully charged - flashes if low battery voltage - flashes for missing battery |
The battery is ready for use The connected battery voltage < 0,5 V/C Battery is missing or incorrect connected |
|
Red and yellow LED 1: - flashes under soft start |
The processor is testing the programme and after about 5 seconds the main charging will start |
| Red
and green LED: - flashes by to high battery voltage while charging |
Battery voltage > 2,9V/C charging charging switches off |
| WU: | This
way of charging can be used for lead/acid batteries, sealed maintenancefree
batteries, Ni-Cd batteries and so on by stationary purposes. (Lift, platform ...) |
|
WU have the following meaning: W : Weak decreasing current U : Constant voltage |
| Main charging will last until the battery is at the gassingpoint. At decreasing current the battery voltage will be held constant. When the charging current is about 30% of main current the yellow LED 2 will illuminate. At the end of the charging event (green LED illuminated) the charging is completed. If the battery remains connected to the battery charger it will get an equalizing current to maintain the battery voltage. At consumption look up section "THE CHARGING EVENT". |
![]() |
| TECHNICAL
DATA |
OPTIONS |
| Back to menu: |
|
* * * * * * * * * * * * * * * * * * |
Processor
controlled Protected against short circuit and for incorrect pole connections Soft start Charging principle according to DIN 41774/41773 Fullautomatic Thyristor controlled Degree of protection IP20/IP54 Constant voltage Adjustable current, adjusted by the manufacture Adjustable voltage, adjusted by the manufacture Independent of mains variations (190-250 volt AC) 75% intermittent use Connect only to the right DC vol- tage Current limited Voltage limited 3 meter output cable (IP20) 3 meter mains cable (IP20) Demko approved (IP20) EMC approved |
* * * * * * * * * * * * * * |
Ammeter Voltmeter Casing in degree of protection up to IP65 or your requires To build-in, degree of protection IP00 Alarm, missing mains Alarm, low battery voltage Alarm, high battery voltage Rippelfilter Temperature regulated charging Boost Oscillating charging Forced-start As you require |
| WARNING! You may not use the battery charger for non recharging batteries. Batteries may generate explosive gas, be careful avoid fire or spark. The battery charger are not designed for charging batteries for cars. Connect the battery charger to earth. The battery charger have to be connected according to present regulation. It may be dangerous to open the battery charger with connected mains. |
| End of SYSTEM LBML/HE Charging principle WU | Back to menu: |
| BATTERY
CHARGER for traction batteries SYSTEM HE Charging principle IUa |
Back to menu: |
![]() |
| FULDAUTOMATIC * * * * * * * * * * * | SOFT START |
| GENERAL
The latest development in the electronic area have been used for these battery chargers. The demand of the battery manufactures has been fulfilled, so the battery obtains highest possible capacity. N.B. The battery charger may only be connected to the DC voltage for which it is designed. (Look up the rating plate). RANGE OF APPLICATION Charging of: Sealed maintenancefree batteries Ni-Cd batteries and so on CHARGING PRINCIPLE, IUa Charges in accordance to DIN 41773, constant current/constant voltage. ![]() CONNECTION 1. Connect the charging cable to the battery via a battery connector. 2. Connect the mains. The charging soft start (red and yellow LED 1 flashes) and after 5 seconds the charging is in function. (Red LED is illuminated). NB!The battery charger may only be connected to the DC voltage for which it is designed. (Look up the rating plate). |
THE
CHARGING EVENT When the charging has started, the fullautomatic battery charger runs and controls the whole charging event. The event can be followed by the coloured LED's. Red LED: - illuminates by main charging - flashes by error Yellow LED 1: - illuminates when the given voltage has been reached Yellow LED 2: - no function by normal charging Green LED: - illuminates when the battery is fully charged - flashes if low battery voltage - flashes for missing battery Red and yellow LED 1: - flashing while soft start (about 5 seconds) DISCONNECTION OF BATTERY Turn off the mains to the battery charger when you disconnect the battery. |
| LED INDICATION: | Back to menu: |
|
Red LED: - illuminates by main charging - flashes by error - flashes by to high battery voltage |
Mains and battery connected correct - Battery voltage is higher than the adjusted value |
| Yellow
LED 1: - illuminates when the given voltage has been reached |
-The gassingpoint of the battery has been reached |
|
Yellow LED 2: - no function by normal charging |
| Green
LED: - illuminates when the battery is fully charged - flashes if low battery voltage - flashes for missing battery |
The battery is ready for use The connected battery voltage < 0,5 V/C Battery is missing or incorrect connected |
|
Red and yellow LED 2: - flashes by too long charging time |
The battery can not keep the gassingpoint within the 10 hour of main charging |
| Red
and yellow LED 1: - flashes under soft start |
The processor is testing the programme and after about 5 seconds the main charging will start |
|
Red and green LED: - flashes by to high battery voltage while charging |
Battery voltage > 2,9V/C charging charging switches off |
| Yellow
2 and green LED: - flashes if battery voltage decreases in the first part of the U-phase |
Defect battery safety cut-out |
| IUa: | This
principle of charging can be used for sealed maintenancefree batteries,
Ni-Cd batteries and so on by traction purposes. |
| IUa
have the following meaning: I : Constant current U : Constant voltage a : Charging completed, stop |
| Main charging time will last max 10 hour. When the current reached 20% of IN, the charging switch to ad- ditional charging. The adjusted voltage will be held constant in the additional time. The additional time is standard graduated after the main charging time i.e. short main charging time will cause short additional charging time. The additional charging time will last max. 4 hour. (N.B. at special programme it can be individual). |
![]() |
| TECHNICAL
DATA |
OPTIONS |
| Back to menu: |
|
* * * * * * * * * * * * * * * * * * * |
Processor
controlled Protected against short circuit and for incorrect pole connections Soft start Charging principle according to DIN 41773 Fullautomatic Thyristor controlled Degree of protection IP20/IP54 Constant current Constant voltage Adjustable current, adjusted by the manufacture Adjustable voltage, adjusted by the manufacture Graduated additional charge Independent of mains variations (190-250 volt AC) Connect only to the right DC vol- tage Current limited Voltage limited 3 meter output cable (IP20) 3 meter mains cable (IP20) Demko approved (IP20) EMC approved |
* * * * * * * * * * * * * * |
Ammeter Voltmeter Casing in degree of protection up to IP65 or your requires To build-in, degree of protection IP00 Alarm, missing mains Alarm, low battery voltage Alarm, high battery voltage Ripplefilter Temperature regulated charging Boost Oscillating charging Forced-start As you require |
| End of SYSTEM HE Charging principle IUa | Back to menu: |
| BATTERY
CHARGER for marine and stationary purposes SYSTEM HE CHARGING PRINCIPLE IU |
Back to menu: |
![]() |
| FULLAUTOMATIC * * * * * * * * * * * | SOFT START |
| GENERAL The latest development in the electronic area have been used for these battery chargers. The demand of the battery manufactures has been fulfilled, so the battery obtains highest possible capacity. N.B. The battery charger may only be connected to the DC voltage for which it is designed. (Look up the rating plate). RANGE OF APPLICATION Charging of: Lead/acid batteries Sealed maintenancefree batteries Ni-Cd batteries and so on CHARGING PRINCIPLE, IU Charges in accordance to DIN 41773, constant current/constant voltage. ![]() CONNECTION 1. Connect the charging cable to the battery by a firm connection. 2. Connect the mains. The charging soft start (red and yellow LED 1 flashes) and after 5 seconds the charging is in function. (Red LED is illuminated). N.B. The battery charger may only be connected to the DC voltage for which it is designed. (Look up the rating plate). |
THE
CHARGING EVENT When the charging has started, the fullautomatic battery charger runs and controls the whole charging event. At consumption the battery charger charges automatically again. The event can be followed by the coloured LED's. ![]() Red LED: - illuminates by main charging - flashes by error Yellow LED 1: - illuminates when the given voltage has been reached Yellow LED 2: - illuminates by I < 30% Green LED: - illuminates when the battery is fully charged - flashes if low battery voltage - flashes for missing battery Red and yellow LED 1: - flashing while soft start (about 5 seconds) DISCONNECTION OF BATTERY Turn off the mains to the battery charger if you disconnect the battery. |
| LED INDICATION: | Back to menu: |
|
Red LED: - illuminates by main charging - flashes by error - flashes by to high battery voltage |
Mains and battery connected correct Battery voltage is higher than the adjusted value |
| Yellow
LED 1: - illuminates when the given voltage has been reached |
The gassingpoint of the battery has been reached |
|
Yellow LED 2: - illuminates by I < 30% |
Main current is less than 30% of nominal current |
| Green
LED: - illuminates when the battery is fully charged - flashes if low battery voltage - flashes for missing battery |
The battery is ready for use The connected battery voltage < 0,5 V/C Battery is missing or incorrect connected |
|
Red and yellow LED 1: - flashes under soft start |
The processor is testing the programme and after about 5 seconds the main charging will start |
|
Red and green LED: - flashes by to high battery voltage while charging |
Battery voltage > 2,9V/C charging charging switches off |
| IU: | This principle of charging can be used for lead/acid batteries, sealed maintenancefree batteries, Ni-Cd batteries and so on by marine and stationary purposes. |
| IU
have the following meaning: I : Constant current U : Constant voltage |
| Main charging will last until the battery is at the gassingpoint. At decreasing current the battery voltage will be held constant. When the charging current is about 30% of main current the yellow LED 2 will illuminate. At the end of the charging event (green LED illuminated) the charging is completed. If the battery remains connected to the battery charger it will get an equalizing current to maintain the battery voltage. At consumption look up section "THE CHARGING EVENT". |
![]() |
| TECHNICAL
DATA |
OPTIONS |
| Back to menu: |
|
* * * * * * * * * * * * * * * * * * * |
Processor
controlled Protected against short circuit and for incorrect pole connections Soft start Charging principle according to DIN 41773 Fullautomatic Thyristor controlled Degree of protection IP20/IP54 Constant current Constant voltage Adjustable current, adjusted by the manufacture Adjustable voltage, adjusted by the manufacture Independent of mains variations (190-250 volt AC) Connect only to the right DC voltage Current limited Voltage limited 3 meter output cable (IP20) 3 meter mains cable (IP20) Demko approved (IP20) EMC approved |
* * * * * * * * * * * * * * |
Ammeter Voltmeter Casing in degree of protection up to IP65 or your requires To build-in, degree of protection IP00 Alarm, missing mains Alarm, low battery voltage Alarm, high battery voltage Rippelfilter Temperature regulated charging Boost Oscillating charging Forced-start As you require |
| WARNING! | Back to menu: |
| You may not use the battery charger for non rechargable batteries. Batteries may generate explosive gas, be careful avoid fire or spark. The battery charger are not designed for charging batteries for cars. Connect the battery charger to earth. The battery charger have to be connected according to present regulation. It may be dangerous to open the battery charger with connected mains. |
| End of BATTERY CHARGER for marine and stationary purpose SYSTEM HE CHARGING PRINCIPLE IU | Back to menu: |
| BATTERY
CHARGER for traction batteries SYSTEM HE CHARGING PRINCIPLE IUIa |
Back to menu: |
![]() Cabinet B9 |
| FULLAUTOMATIC * * * * * * * * * * * | SOFT START |
| GENERAL
The latest development in the electronic area have been used for these battery chargers. The demand of the battery manufactures has been fulfilled, so the battery obtains highest possible capacity. N.B. The battery charger may only be connected to the DC voltage for which it is designed. (Look up the rating plate). RANGE OF APPLICATION Charging of: Lead/acid batteries CHARGING PRINCIPLE, IUIa Charges in accordance to DIN 41773, constant current/constant voltage. CONNECTION 1. Connect the charging cable to the battery via a battery connector. 2. Connect the mains. The charging soft start (red and yellow LED 1 flashes) and after 5 seconds the charging is in function. (Red LED is illuminated). N.B. The battery charger may only be connected to the DC voltage for which it is designed. (Look up the rating plate). |
THE
CHARGING EVENT When the charging has started, the fullautomatic battery charger runs and controls the whole charging event. The event can be followed by the coloured LED's. Red LED: - illuminates by main charging - flashes by error Yellow LED 1: - illuminates when the given voltage has been reached Yellow LED 2: - illuminates by additional charging Green LED: - illuminates when the battery is fully charged - flashes if low battery voltage - flashes for missing battery Red and yellow LED 1: - flashing while soft start (about 5 seconds) DISCONNECTION OF BATTERY Turn off the mains to the battery charger when you disconnect the battery. |
| LED INDICATION: | Back to menu: |
|
Red LED: - illuminates by main charging - flashes by error - flashes by to high battery voltage |
Mains and battery connected correct Battery voltage is higher than the adjusted value |
| Yellow
LED 1: - illuminates when the given voltage has been reached |
The gassingpoint of the battery has been reached |
|
Yellow LED 2: - illuminates by additional charging - illuminates by trickle charge |
The charging is in I2-phase Trickle charge for 3 min., every hour |
| Green
LED: - illuminates when the battery is fully charged - not illuminated by trickle charge - flashes if low battery voltage - flashes for missing battery |
The battery is ready for use Yellow LED 2 illuminates The connected battery voltage < 0,5 V/C Battery is missing or incorrect connected |
|
Red and yellow LED 2: - flashes by too long charging time |
The battery can not keep the gassingpoint within the 10 hour of main charging |
| Red
and yellow LED 1: - flashes under soft start |
The processor is testing the programme and after about 5 seconds the main charging will start |
|
Red and green LED: - flashes by to high battery voltage while charging |
Battery voltage > 2,9V/C charging switches off |
| Yellow
2 and green LED: - flashes if battery voltage decreases in the first part of the U-phase |
Defect battery safety cut-out |
| IUIa: | This
principle of charging can be used for lead/acid batteries by traction purposes.
IUIa have the following meaning: |
| I1
: Constant current I1-phase U : Constant voltage U-phase I2 : Constant current I2-phase a : Charging completed, if the battery remains connected it will get trickle charging |
| Main
charging time (I1-phase + U-phase) will last max 10 hour. When the current
in the U-phase reached the point where the I2 current start the I2-phase
will do the additional charging. Charging time in this phase is max. 4 hour.
If the main charging is less than 4 hour, the additional time will be as
long as the main charging. The current in the I2-phase can be from 6% to
50% of IN (main charging current). When the additional charging has finished
the charging will stop for 30 minutes and then a sequence of trickle charge
will start for 3 minutes every hour. The trickle charge can be 4% to 25%
of the IN, (main charging current). |
![]() |
| TECHNICAL
DATA |
OPTIONS |
| Back to menu: |
|
* * * * * * * * * * * * * * * * * * * |
Processor
controlled Protected against short circuit and for incorrect pole connections Soft start Charging principle according to DIN 41773 Fullautomatic Thyristor controlled Degree of protection IP20/IP54 Constant current Constant voltage Adjustable current, adjusted by the manufacture Adjustable voltage, adjusted by the manufacture Graduated additional charge Independent of mains variations (190-250 volt AC) Connect only to the right DC voltage Current limited Voltage limited 3 meter output cable (IP20) 3 meter mains cable (IP20) Demko approved (IP20) EMC approved |
* * * * * * * * * * * * * * |
Ammeter Voltmeter Casing in degree of protection up to IP65 or your requires To build-in, degree of protection IP00 Alarm, missing mains Alarm, low battery voltage Alarm, high battery voltage Rippelfilter Temperature regulated charging Boost Oscillating charging Forced-start As you require |
| WARNING!
You may not use the battery charger for non rechargable batteries. Batteries may generate explosive gas, be careful avoid fire or spark. The battery charger are not designed for charging batteries for cars. Connect the battery charger to earth. The battery charger have to be connected according to present regulation. It may be dangerous to open the battery charger with connected mains. |
| End of System HE CHARGING PRINCIPLE IUIa | Back to menu: |